MARK Climate Technology distributor in TürkiyeElburz Mühendislik
Adiabatic Cooling
Adiabatic cooling and fresh air for large production halls with MARK COLDSTREAM. Assess evaporative cooling against your local climate and the air balance of your facility.

Supply cooler outdoor air for summer working conditions
How does it work?
COLDSTREAM passes outdoor air through wetted pads. Evaporation cools the air while increasing its moisture content; the result depends on local temperature and humidity.
Where does it fit?
Production halls and large working areas in suitable climates. Air needs an adequate discharge route; humid climates and moisture-sensitive processes require separate assessment.
Technical features and product options
MARK COLDSTREAM cools outdoor air by passing it through a water-wetted cellulose filter pack. Evaporation lowers the air’s sensible temperature while increasing its moisture content. The system is intended for ventilation and summer comfort in large spaces.
| Feature | Technical information |
|---|---|
| Operating principle | Direct evaporative cooling based on water evaporation |
| Air side | Outdoor air, fan and high-efficiency cellulose filter pack |
| Water circuit | Pump-driven distribution system and electrical shut-off valve at the water inlet |
| Automatic functions | Water replacement, drainage and cleaning |
| Controls | Temperature, fan speed and relative-humidity control; daily/weekly programming |
| Operating modes | Ventilation and/or cooling |
A fixed supply temperature or identical temperature reduction in every climate cannot be promised. Performance depends on outdoor dry-/wet-bulb conditions, selected airflow and the building air balance.
TA209 and TC209 model comparison
| Parameter | TA209 | TC209 |
|---|---|---|
| Fan type | Axial | Centrifugal |
| Maximum airflow | 20,000 m³/h | 20,000 m³/h |
| Minimum airflow | 10,000 m³/h | 10,000 m³/h |
| Power supply | 230 V / ~50 Hz | 400 V / 3N~50 Hz |
| Electrical power consumption | 1.8 kW | 3.2 kW |
| Reference water consumption* | 64 L/h | 64 L/h |
| Pad thickness / area | 100 mm / 3.4 m² | 100 mm / 3.4 m² |
| Pad saturation efficiency | 88% | 88% |
| Empty / full weight | 120 / 146 kg | 160 / 186 kg |
*The manual’s water-consumption test condition is 33 °C outdoor temperature and 60% relative humidity. Actual water use and cooling depend on climate and operation. The 88% pad saturation efficiency is not an electricity-saving percentage. Electrical power consumption is not cooling capacity. Check airflow against duct losses and confirm the model and supply configuration at quotation stage.
Project selection and installation
Climate and humidity
Start with local summer design temperature and relative humidity. Limited evaporation potential restricts achievable cooling. For humidity-sensitive processes, also check allowable indoor conditions.
Air distribution and relief
Coordinate distribution to occupied zones with a route for indoor air to leave the building. Internal heat gains, doors and existing extraction systems affect the required airflow.
Water, maintenance and scheduling
Plan water supply, drainage, water quality and access to the filter pack. Automatic cleaning does not remove the need for maintenance; follow the manufacturer’s seasonal and operational procedures.
Why consider it for large production halls?
Frequent door opening, process heat and continuous air-change requirements can make conventional closed-space air conditioning difficult in large facilities. COLDSTREAM combines outdoor-air ventilation with evaporative cooling. Electricity is used by the fan and water circuit without a refrigeration compressor. A feasibility assessment should compare electricity and water use with the required occupied-zone conditions.
Common questions
Does it provide the same result as compressor-based air conditioning?
No. Direct evaporative cooling adds moisture and depends on outdoor conditions. Applications requiring precise temperature and humidity control need a separate system assessment.
How is it selected for humid locations?
Do not select by location name alone. Evaluate coincident design temperature and humidity, then calculate expected conditions using the target indoor requirements and airflow.
Should doors and windows remain closed?
Supply air must be able to leave the building. The manual explains that closing relief openings reduces cooling and increases indoor humidity. Size relief openings or mechanical extraction together with the air-distribution system.
Technical documents
Consult MARK’s product information and technical manuals for model selection, installation and maintenance.
Sources checked: 15 November 2026. Final selection must be verified against project conditions and the current manufacturer documentation for the selected model.
Let’s discuss your project
Share your application and project requirements. We coordinate product selection, quotation and supply with MARK.
